Main Features:
1. Cooling range 7-25℃; Stainless steel inculated water tank.
2. Equipped with anti-freeze thermostat.
3. Adopt ozone-friendly refrigerant R410A, used to improve coefficient of performance(COP).
4. Refrigerant loop controlled by high and low pressure switches to ensure stable operation.
5. Comppressor and pump overload protection.
6. Adopt precise high-precision temperature controller with an accuracy of ±1℃。
7. Single compressor system series are equipped with low pressure pump, and model with two or more systems are
equipped with medium pressure pump.
8. All adopt well known and quality compressors.
9. Adopt fin style condenser design. Without any need of cooling water for excellent heat transfer and rapid cooling.
Parametrs of SIC-A-R2 Series(50Hz)
Hautek will recommend you proper air coolled chiller according to the model of your blowing machine.
Model | SIC-7.5A-R2 | SIC-12A-R2 | SIC-18A-R2 | SIC-24A-R2 | SIC-28A-R2 |
Refrigerant Capacity(1) | kw | 7.5 | 12 | 18 | 24 | 28 |
Refrigerant Capacity(2) | kw | 9.5 | 14 | 24 | 32 | 38 |
Compressor | Type | Scroll |
Power (kw) | 2.9 | 4.2 | 6.4 | 8.72 | 9.36 |
Refrigerant | Filling Volume (kg) | 3.5 | 5 | 5.5 | 5.5 | 9 |
Control Mode | Thermostatic expansion valve |
Type | R410A |
Evaporator | Type | Tube-in-shell style |
Condenser | Type | Fin style |
Blower (KW) | 0.19 | 0.55 | 2x0.23 | 2x0.385 | 2x0.6 |
Water tank capacity(L) | | 30 | 30 | 65 | 65 | 80 |
Pump(4) | Power(KW) | 0.75/0.75/1.1 | 1.1/1.1/1.1 | 1.1/1.5/2.2 |
Pump flow(L/min) | 21.5 | 34.4 | 51.6 | 68.8 | 80.3 |
Working Pressure(kgf/cm2)(3) | 3.3/3.7/4.5 | 3.2/3.5/4.4 | 2.8/4.1/4.9 | 2.7/2.35/4.5 | 3.1/3.9/4.9 |
Total power | Total Power(KW) (5) | 3.8/3.8/4.2 | 5.5/5.5/5.9 | 7.8/7.8/7.8 | 10.6/10.6/10.6 | 11.7/12/12.8 |
Pipe coupling(inch) | Chilled water outlet | 1 | 1 1/2 |
Chilled water inlet | 1 | 1 1/2 |
Water tank drainage port | 1/2 |
Water tank overflow port | 1/2 |
Protective devices | Compressor | Overload relay |
Pump | Overload relay |
Refrigerant circuit | High and low pressure switch/Anti-freeze switch |
Cooling water circuit | By-pass valve/Water level switch(option)/Flow switch |
Power(VAC)(6) | 3Phase, 400VAC, 50Hz |
Measures exchange | 1kw=860 kcal/hr 1RT=3.024 kcal/hr 10.000 Btu/hr=2.520 kcal/hr |
Model | SIC-38A-R2 | SIC-48A-R2 | SIC-58A-R2 | SIC-75A-R2 |
Refrigerant Capacity(1) | kw | 38 | 48 | 58 | 75 |
Refrigerant Capacity(2) | kw | 45 | 64 | 76 | 90 |
Compressor | Type | Scroll |
Power (kw) | 12.25 | 17.44 | 18.72 | 24.86 |
Refrigerant | Filling Volume (kg) | 12.5 | 7.5x2 | 8x2 | 8x2 |
Control Mode | Thermostatic expansion valve |
Type | R410A |
Evaporator | Type | Tube-in-shell style |
Condenser | Type | Fin style |
Blower (KW) | 2x0.78 | 2x1.03 | 2x0.85 | 2x1.92 |
Water tank capacity(L) | | 80 | 186 | 186 | 230 |
Pump(4) | Power(KW) | 1.1/1.5/2.2 | -/1.8/2.4 | -/3.0/4.0 |
Pump flow(L/min) | 108.9 | 137.6 | 166.3 | 215 |
Working Pressure(kgf/cm2)(3) | 2.4/3.8/4.6 | -/3.4/4.5 | -/3.2/4.3 | -/3.5/4.1 |
Total power | Total Power(KW) (5) | 14.9/15.3/16 | -/21.3/21.9 | -/22.2/22.8 | -/31.7/32.7 |
Pipe coupling(inch) | Chilled water outlet | 2 | 2 1/2 |
Chilled water inlet | 2 | 2 1/2 |
Water tank drainage port | 1/2 | 1 |
Water tank overflow port | 1/2 |
Protective devices | Compressor | Overload relay |
Pump | Overload relay |
Refrigerant circuit | High and low pressure switch/Anti-freeze switch |
Cooling water circuit | By-pass valve/Water level switch(option)/Flow switch |
Power(VAC)(6) | 3Phase, 400VAC, 50Hz |
Measures exchange | 1kw=860 kcal/hr 1RT=3.024 kcal/hr 10.000 Btu/hr=2.520 kcal/hr |
Note:
1) Refrigeration capacity 1 is based on the flow of 0.172m3/(h.k.W), the chilled water outlet temperature of 7℃ and the environment temperature 35℃.
2) Refrigeration capacity 2 is based on the flow of 0.172m3/(h.k.W), the chilled water outlet temperature of 15℃ and the environment temperature 25℃.
3) It is the working pressure of water pump when negative pressure of inlet water is 0.
4) Low pressure pump is for domestic and Southest Asia export, customers can change for medium pressure pumps(use P for short; e.g.:SIC-and A-R2-P) or high pressure pumps(use HP for short; e.g.:SIC-and A-R2-HP), specific parameters in turn as shown above.
5) Pump power is included in total power.
6) Special orders of machine voltage can be acceptable according to customers's request.
7) The air-cooled water chiller is applicable to the conditions under the environment temperature of 43℃.
Parametrs of SIC-A-R2 Series(60Hz)
Hautek will recommend you proper air coolled chiller according to the model of your blowing machine.
Model | SIC-12A-R2 | SIC-24A-R2 | SIC-28A-R2 | SIC-38A-R2 |
Refrigerant Capacity(1) | kw | 15 | 30 | 35.5 | 45 |
Refrigerant Capacity(2) | kw | 17.5 | 37.5 | 41 | 48 |
Compressor | Type | Scroll |
Power (kw) | 5.28 | 10.2 | 11.73 | 14.8 |
Refrigerant | Filling Volume (kg) | 5 | 5.5 | 9 | 12.5 |
Control Mode | Thermostatic expansion valve |
Type | R410A |
Evaporator | Type | Plate evaporator |
Condenser | Type | Fin style |
Blower (KW) | 0.91 | 2x0.57 | 2x0.91 | 2x1.1 |
Water tank capacity(L) | | 50 | 85 | 150 | 150 |
Pump(4) | Power(KW) | 0.75/1.5 | 1.1/1.5 | 2.2/3.0 | 2.2/3.0 |
Pump flow(L/min) | 43.1 | 86.2 | 102 | 129.3 |
Working Pressure(kgf/cm2)(3) | -/3.1/5.1 | -/3.0/4.2 | -/2.7/4.1 | -/2.5/3.9 |
Total power | Total Power(KW) (5) | -/6.9/7.6 | -/12.4/12.8 | -/15.7/16.5 | -/19.2/20 |
Pipe coupling(inch) | Chilled water outlet | 1 | 1 1/2 | 2 |
Chilled water inlet | 1 | 1 1/2 | 2 |
Water tank drainage port | 1/2 | 1/2 | 1/2 | 1/2 |
Water tank overflow port | 1/2 |
Protective devices | Compressor | Overload relay |
Pump | Overload relay |
Refrigerant circuit | High and low pressure switches/Anti-freeze switch |
Cooling water circuit | By-pass valve/Water level switch(option)/Flow switch |
Power(VAC)(6) | 3Phase, 230/400/460/575VAC, 60Hz |
Measures exchange | 1kw=860 kcal/hr 1RT=3.024 kcal/hr 10.000 Btu/hr=2.520 kcal/hr |
Model | SIC-48A-R2 | SIC-58A-R2 | SIC-75A-R2 | SIC-100A-R2 | SIC-114A-R2 |
Refrigerant Capacity(1) | kw | 60 | 70 | 90 | 122 | 136 |
Refrigerant Capacity(2) | kw | 75 | 82 | 96 | 133.5 | 144 |
Compressor | Type | Scroll |
Power (kw) | 20.4 | 23.76 | 29.6 | 39.8 | 44.4 |
Refrigerant | Filling Volume (kg) | 7.5x2 | 8x2 | 8x2 | 7.8x2+6.8 | 8.7x3 |
Control Mode | Thermostatic expansion valve |
Type | R410A |
Evaporator | Type | Plate evaporator |
Condenser | Type | Fin style |
Blower (KW) | 2x2.2 | 2x2.2 | 2x2.2 | 2x2.2+2.2 | 3x2.2 |
Water tank capacity(L) | | 180 | 200 | 270 | 400 | 400 |
Pump(4) | Power(KW) | 3.0/3.0 | 3.0/3.0 | 5.5/5.5 | 5.5/5.5 | 5.5/5.5 |
Pump flow(L/min) | 172.3 | 201.1 | 258.5 | 350.4 | 390.7 |
Working Pressure(kgf/cm2)(3) | -/4.5/5.6 | -/3.9/4.8 | -/2.8/2.8 | -/4.5/4.5 | -/4.1/4.1 |
Total power | Total Power(KW) (5) | 27.8 | 31.1 | 39.5 | 51.9 | 56.5 |
Pipe coupling(inch) | Chilled water outlet | 2 | 2.5 |
Chilled water inlet | 2 | 2.5 |
Water tank drainage port | 1 | 1 | 1 | 1 | 1 |
Water tank overflow port | 1/2 | 1 |
Protective devices | Compressor | Overload relay |
Pump | Overload relay |
Refrigerant circuit | High and low pressure switches/Anti-freeze switch |
Cooling water circuit | By-pass valve/Water level switch(option)/Flow switch |
Power(VAC)(6) | 3Phase, 230/400/460/575VAC, 60Hz |
Measures exchange | 1kw=860 kcal/hr 1RT=3.024 kcal/hr 10.000 Btu/hr=2.520 kcal/hr |
Note:
1) Refrigeration capacity 1 is based on the flow of 0.172m3/(h.k.W), the chilled water outlet temperature of 7℃ and the environment temperature 35℃.
2) Refrigeration capacity 2 is based on the flow of 0.172m3/(h.k.W), the chilled water outlet temperature of 20℃ and the environment temperature 30℃.
3) It is the working pressure of water pump when negative pressure of inlet water is 0.
4) Low pressure pump is for domestic and Southest Asia export, customers can change for medium pressure pumps(use P for short; e.g.:SIC-and A-R2-P) or high pressure pumps(use HP for short; e.g.:SIC-and A-R2-HP), specific parameters in turn as shown above.
5) Pump power is included in total power.
6) Special orders of machine voltage can be acceptable according to customers's request.
7) The air-cooled water chiller is applicable to the conditions under the environment temperature of 43℃.